With the RUN command ON, when the free-run state is canceled after the Power Interruption Re-
start Wait Time (H13) has elapsed since the free-run state, the frequency selected by Starting Fre-
quency Selection at Frequency Pull-in Restart (E152) is output and the frequency pull-in restart is
performed.
The examples below assume that the FRS terminal is used.
Example) When Starting Frequency Selection at Frequency Pull-in Restart (E152) = “0: Frequency
at which the power failure occurred”
FW
FRS terminal
Output frequency
(Motor rotation speed)
Power Interruption
Restart Wait Time (H13)
Free Run Stop Restart
Allowable Time (H440)
Example) When Starting Frequency Selection at Frequency Pull-in Restart (E152) = “3: Starting fre-
quency”
Power Interruption
Restart Wait Time (H13)
Free Run Stop Restart
Allowable Time (H440)
FW
FRS terminal
Output frequency
(Motor rotation speed)
Frequency Reference
Starting frequency
7 Other Functions
7-62
M1 Series Standard Type User's Manual (I669)