132
"C" Group: Intelligent Terminal Functions Section 3-7
02 CF1 *1 Multi-speed Select,
Bit 0 (LSB)
ON Binary encoded speed select, Bit 0, logical 1
OFF Binary encoded speed select, Bit 0, logical 0
03 CF2 Multi-speed Select,
Bit 1
ON Binary encoded speed select, Bit 1, logical 1
OFF Binary encoded speed select, Bit 1, logical 0
04 CF3 Multi-speed Select,
Bit 2
ON Binary encoded speed select, Bit 2, logical 1
OFF Binary encoded speed select, Bit 2, logical 0
05 CF4 Multi-speed Select,
Bit 3 (MSB)
ON Binary encoded speed select, Bit 3, logical 1
OFF Binary encoded speed select, Bit 3, logical 0
06 JG Jogging ON Inverter is in Run Mode, output to motor runs at jog
parameter frequency
OFF Inverter is in Stop Mode
07 DB External DC braking ON DC braking will be applied during deceleration
OFF DC braking will not be applied
08 SET Set (select) 2
nd
motor
Data
ON The inverter uses 2
nd
motor parameters for generat-
ing frequency output to motor
OFF The inverter uses 1st (main) motor parameters for
generating frequency output to motor
09 2CH 2-stage Acceleration
and Deceleration
ON Frequency output uses 2nd-stage acceleration and
deceleration values
OFF Frequency output uses standard acceleration and
deceleration values
11 FRS Free-run Stop ON Causes output to turn OFF, allowing motor to free
run (coast) to stop
OFF Output operates normally, so controlled deceleration
stop motor
12 EXT External Trip ON When assigned input transitions OFF to ON, inverter
latches trip event and displays E 12
OFF No trip event for ON to OFF, any recorded trip events
remain in history until reset
13 USP Unattended Start Pro-
tection
ON On powerup, the inverter will not resume a Run com-
mand
OFF On powerup, the inverter will resume a Run com-
mand that was active before power loss
14 CS Commercial power
source switchover
ON Motor can be driven by commercial power
OFF Motor is driven via the inverter
15 SFT Software Lock ON The keypad and remote programming devices are
prevented from changing parameters
OFF The parameters may be edited and stored
16 AT Analog Input Voltage/
Current Select
ON Refer to Analog Input Settings on page 71.
OFF
18 RS Reset Inverter ON The trip condition is reset, the motor output is turned
OFF, and powerup reset is asserted
OFF Normal power-ON operation
19 PTC PTC thermistor Thermal
Protection
(C005 only)
ANLG When a thermistor is connected to terminal [5] and
[L], the inverter checks for over-temperature and will
cause trip event and turn OFF output to motor
OPEN A disconnect of the thermistor causes a trip event,
and the inverter turns OFF the motor
20 STA Start
(3-wire interface)
ON Starts the motor rotation
OFF No change to present motor status
21 STP Stop
(3-wire interface)
ON Stops the motor rotation
OFF No change to present motor status
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description