"D" Group: Monitoring Functions Section 3-3
3-3 "D" Group: Monitoring Functions
You can access important parameter values with the "D" Group monitoring
functions, whether the inverter is in Run Mode or Stop Mode. After selecting
the function code number for the parameter you want to monitor, press the
Function key once to show the value on the display. In functions
D005 and
D006, the intelligent terminals use individual segments of the display to show
ON/OFF status.
If the inverter display is set to monitor a parameter and powerdown occurs,
the inverter stores the present monitor function setting. For your convenience,
the display automatically returns to the previously monitored parameter upon
the next powerup.
"D" Function Run
Mode
Edit
Units
Func.
Code
Name Description
D001 Output frequency monitor Real time display of output frequency to motor
from 0.0 to 400.0Hz
*1
If b163 is set high, out-
put frequency (F001) can be changed by up/
down key with d001 monitoring.
–Hz
D002 Output current monitor Filtered display of output current to motor,
range is 0 to 655.3 ampere (~99.9 ampere for
1.5kW and less)
–A
D003 Rotation direction monitor Three different indications:
"F" ...Forward
"o" ...Stop
"r" ...Reverse
––
D004 Process variable (PV), PID feed-
back monitor
Displays the scaled PID process variable
(feedback) value (A075 is scale factor), 0.00 to
10000
–-
D005 Intelligent input terminal status Displays the state of the intelligent input termi-
nals:
––
D006 Intelligent output terminal status Displays the state of the intelligent output ter-
minals:
––
D007 Scaled output frequency monitor Displays the output frequency scaled by the
constant in B086. Decimal point indicates
range: 0 to 40000
–-
d008 Actual frequency monitor Displays the actual frequency, range is
-400 to 400 Hz
*2
–Hz
d009 Torque command monitor Displays the torque command, range is
-200 to 200%
–%
d010 Torque bias monitor Displays the torque bias value, range is
-200 to 200%
–%
d012 Output torque monitor Displays the output torque, range is -200 to
200%
–%
D013 Output voltage monitor Voltage of output to motor, Range is 0.0 to
600.0 V
–V
d014 Input power monitor Displays the input power, range is 0 to 100 kW KW
d015 Watt-hour monitor Displays watt-hour of the inverter, range is 0 to
9999000
––
D016 Elapsed RUN time monitor Displays total time the inverter has been in
RUN mode in hours. Range is 0 to 9999 /
1000 to 9999 / 100 to 999 (10,000 to 99,900)
hours
ON
OFF
7 654321
Terminal numbers
ON
OFF
Relay 11 12