EasyManuals Logo
Home>Omron>Inverter>MX2

Omron MX2 User Manual

Omron MX2
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #245 background imageLoading...
Page #245 background image
223
Analog Input Operation Section 4-7
4-7 Analog Input Operation
The MX2 inverters provide for analog input
to command the inverter frequency output
value. The analog input terminal group
includes the [L], [OI], [O], and [H] terminals
on the control connector, which provide for
Voltage [O] or Current [OI] input. All analog
input signals must use the analog ground [L].
If you use either the voltage or current ana-
log input, you must select one of them using
the logic input terminal function [AT] analog
type. Refer to the table on next page show-
ing the activation of each analog input by
combination of
A005 set parameter and [AT]
terminal condition. The [AT] terminal function
is covered in "Analog Input Current/Voltage
Select" in section 4. Remember that you
must also set
A001 = 01 to select analog input
as the frequency source.
Note If no logic input terminal is configured for the [AT] function, then inverter rec-
ognizes that [AT]=OFF and MCU recognizes [O]+[OI] as analog input. In case
either (O) or (OI) is to be refered, please ground the other.
Using an external potentiometer is a com-
mon way to control the inverter output fre-
quency (and a good way to learn how to use
the analog inputs). The potentiometer uses
the built-in 10 V reference [H] and the analog
ground [L] for excitation, and the voltage
input [O] for the signal. By default, the [AT]
terminal selects the voltage input when it is
OFF.
Take care to use the proper resistance for
the potentiometer, which is 1~2kΩ, 2 Watts.
Voltage Input – The voltage input circuit
uses terminals [L] and [O]. Attach the signal
cable's shield wire only to terminal [L] on the
inverter. Maintain the voltage within specifi-
cations (do not apply negative voltage).
Valid for inputs: 11 Dedicated to terminal [11]:
Required settings:
Option
Code
Terminal
Symbol
Function
Name
State Description
RY
Inverter output
terminal circuit
CM2 11
EDM
AM H O OI L
+V Ref.
Voltage input
Current input
A
GND
AM H O OI L
Freq.
setting
V/I input select
[AT]
+
-
4-20 mA
0-10 V
A001
AM H O OI L
1 to 2kΩ, 2 W
0 to 9.6 VDC,
0 to 10 V nominal
AM H O OI L
+
-

Table of Contents

Other manuals for Omron MX2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 and is the answer not in the manual?

Omron MX2 Specifications

General IconGeneral
BrandOmron
ModelMX2
CategoryInverter
LanguageEnglish

Related product manuals