EasyManuals Logo
Home>Rockwell Automation>Industrial Equipment>Allen-Bradley PowerFlex 755T Flux Vector Tuning

Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning User Manual

Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
98 Rockwell Automation Publication 750-AT006D-EN-P - January 2022
Chapter 6 Active Front End Tuning
internal regulator can turned on and off using 13:40 [Conv Options Config] Bit 3 Cfg:VarDCBAdjDis and fine tuned, if needed, using 13:82
[BusAutoAdjReg Kp] and 13:83 [BusAutoAdjReg Ki]. Table 35 summarizes the reactive power control parameters. Figure 81 shows a simplified
block diagram of this function.
Figure 79 - Simplified Equivalent Circuit of Power Converter Connected to Grid Source
Figure 80 - Phasor Diagram of the Converter Current
Table 35 - Reactive Power Control Function Parameter Settings
Parameter No. Parameter Name Description
13:40 [Conv Options Cfg]
Converter Options
Configuration
Bit 3 VarDCBAdjDis disables the Var control DC bus automatic adjustment feature.
This feature is active only when 13:45 [DC Bus Reference Sel] is set to VAR Control (3).
It automatically raises the DC bus level to allow for Var control.
Bit 7 VAR OnlyMode enables the line-side converter to produce reactive power only.
In this mode, the whole rating of the power structure is dedicated for reactive power compensation.
The converter does not provide any active power to loads connected to the DC bus.
13:69 [kVAR Ref]
Reactive Power
Reference
Enter a value to set the Reactive Power (kVAR) reference.
Negative values command a leading power factor (injecting reactive power to the line) and positive values
command a lagging power factor (consuming reactive power from the line).
When the value is zero, the line-side converter will regulate reactive current to maintain a unity power
factor.
If the line-side converter is not in Reactive Power Only mode
(13:40 [Conv Options Config] Bit 7 Cfg:VAR OnlyMode is cleared), the line-side converter prioritizes the
active power needs of the loads connected to the DC bus.
The line-side converter dedicates its remaining capacity to reactive power.
13:70 [kVAR Rate Limit]
Reactive Power Rate
Limit
Enter a value to set the maximum rate of change for the Reactive Power when the Reactive Power reference
is non-zero.
13:71 [kVAR Available]
Reactive Power
Available
Displays available Reactive Power based on the rating and the load of the line-side converter.
13:72 [kVAR Command]
Reactive Power
Command
Displays the limited and conditioned Reactive Power reference.
The Reactive Power regulator consumes this signal as its command.
V
conv
V
grid
L
V
conv
I
conv
X
V
grid
I
conv
V
conv
V
grid
I
conv
I
conv
X
V
conv
V
grid
I
conv
I
conv
X
at Unity Power Factor Injecting Reactive Power to the Grid (Lag) Absorbing Reactive Power from the Grid (Lead)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 755T Flux Vector Tuning
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals