6.1.2 Proper EMC installation of drives (installation instructions)
6.1.2.1 General
Since drives can be operated in a wide range of differing environments and the electrical
components used (controls, switched-mode power supplies, etc.) can widely differ with respect to
noise immunity and radiation, any mounting/installation guideline can only represent a practical
compromise. For this reason, EMC regulations do not need to be implemented to the letter,
provided that measures are checked out on a case by case basis.
In order to guarantee electromagnetic compatibility in your cabinets in rugged electrical
environments and fulfil the standards specified by the relevant regulatory bodies, the following EMC
regulations must be observed when designing and installing cabinets.
Rules 1 to 10 generally apply. Rules 11 to 15 must be followed to fulfil standards governing radiated
noise.
6.1.2.2 Rules for proper EMC installation
Rule 1
All the metal components in the cabinet must be conductively connected over a large surface area
with one another (not paint on paint!). Serrated or contact washers must be used where necessary.
The cabinet door should be connected to the cabinet through the shortest possible grounding straps
(top, center, bottom)..
Rule 2
Contactors, relays, solenoid valves, electromechanical hours counters, etc. in the cabinet, and, if
applicable, in adjacent cabinets, must be provided with quenching elements, for example, RC
elements, varistors, diodes. These devices must be connected directly at the coil.
Rule 3
Signal cables
1)
should enter the cabinet at only one level wherever possible.
Rule 4
Unshielded cables in the same circuit (incoming and outgoing conductors) must be twisted where
possible, or the area between them kept as small as possible in order to prevent unnecessary
coupling effects.
Rule 5
Connect spare conductors to the cabinet ground (ground
2)
) at both ends to obtain an additional
shielding effect.
Rule 6
Avoid any unnecessary cable lengths in order to reduce coupling capacitances and inductances.
Rule 7
Crosstalk is kept low if cables are routed close to the cabinet ground. For this reason, wiring should
not be routed freely in the cabinet, but as close as possible to the cabinet frame and mounting
panels. This applies equally to spare cables.
Rule 8
Signal and power cables must be routed separately from one another (to prevent noise from being
coupled in). A minimum 20 cm clearance should be maintained.
If the encoder cables and motor cables cannot be routed separately, then the encoder cable must
be decoupled by means of a metal partition or installation in a metal pipe or duct. The partition or
metal duct must be grounded at several points.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOREG DC Master 6RA7018-6DS22 and is the answer not in the manual?

Siemens SIMOREG DC Master 6RA7018-6DS22 Specifications

General IconGeneral
BrandSiemens
ModelSIMOREG DC Master 6RA7018-6DS22
CategoryServo Drives
LanguageEnglish

Related product manuals