5.3.2 Properties of the user memory
Non‑volatile data
Non‑volatile data make it possible to retain relevant data for the user and the system even
when
the SIMOTION D4x5‑2 has been switched off. Information about the area which can be
used for non-volatile data is available in the
SIMOTION D4x5‑2, Technical Data
Manual.
A SIMOTION device has the following non‑volatile data:
Table 5-1 Non‑volatile data contents
Non-volatile data Content
Kernel data
Last operating mode
IP parameters (IP address, subnet mask, router address)
DP parameters (PROFIBUS DP address, baud rate)
Diagnostic buffer
Retain variables
Variables
in the interface or implementation section of a unit declared with
VAR_GLOBAL RETAIN
Global device variables set with the "RETAIN" attribute
Retain TO Absolute encoder offset
DCC blocks SAV blocks and user-defined blocks with retain behavior ("SAV = SAVE",
blocks for the non-volatile data backup).
NVRAM (SINAMICS) For the SINAMICS Integrated, CX32-2 and SINAMICS S120 CU310-2/
CU320-2,
data protected against loss at power failure is called NVRAM data
or non-volatile data.
Note
DCC
SIMOTION blocks with retain behavior act like retain variables in terms of copying RAM
to ROM, resetting memory, downloading, backing up non‑volatile SIMOTION data
(_savePersistentMemoryData) and backing up data.
For the SINAMICS Integrated and CX32‑2, the data backup of the SINAMICS retain data (and
therefore also for SINAMICS DCC) is performed via the NVRAM (D4x5‑2) or the FRAM
(CX32‑2). SINAMICS data is not saved with _savePersistentMemoryData. The non-volatile
SINAMICS data (NVRAM data) is backed up by setting the CU parameter p7775 to 1.
For further information on DCC, see the
DCC Programming
Programming Manual.
Commissioning (hardware)
5.3 User memory concept
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B 103

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D4x5-2 and is the answer not in the manual?

Siemens SIMOTION D4x5-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D4x5-2
CategoryControl Unit
LanguageEnglish

Related product manuals