SIMOTION D4x5‑2 module replacement without PG/PC
To
enable a module replacement without a PG/PC, you must back up the current non-volatile
SIMOTION and SINAMICS data on the CF card during operation.
NOTICE
Loss of data due to failure to make backup copies
Non-backed-up non-volatile SIMOTION data can be lost on hardware replacement (module
defect), for example, if the current value of the retain variables have not been backed up and
replaced by their initial values again.
Back up the non-volatile SIMOTION data on the CF card.
NOTICE
Repeat referencing necessary after absolute encoder overflow
If
an absolute encoder overflow occurs after _savePersistentMemoryData, the actual position
value is no longer correct after the non-volatile SIMOTION data are restored.
In this case, homing (absolute encoder adjustment) must be repeated.
See also
Parts replacement for SIMOTION D4x5-2 (Page 341
)
Operations and their effect on the user memory (Page 106)
Replacing modules in the spare part scenario (Page 114)
8.2.3 Replacing DRIVE-CLiQ components
Module replacement
DRIVE-CLiQ components not only support replacement in the switched-off state of the
machine/system (Power Off), but also a replacement during operation. For this, the component
to be replaced must be at the end of the DRIVE-CLiQ line.
Requirement
The affected components are located at the end of the line.
If an infeed is affected, the power units supplied by it do not function.
Service and maintenance
8.2 Replacing modules (spare part scenario)
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B 343

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D4x5-2 and is the answer not in the manual?

Siemens SIMOTION D4x5-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D4x5-2
CategoryControl Unit
LanguageEnglish

Related product manuals