Further information
For further information, see the
SIMOTION Communication
System Manual.
6.5.2.5 PROFINET V2.3: Optimized data transfer / 125 µs PROFINET send cycle clock
All SIMOTION D4x5‑2 DP/PN Control Units support PROFINET according to the
PI specification PN V2.3. For SIMOTION D455‑2 DP/PN, the optional functionality
Performance Upgrade is available, which provides the following functional scope:
Reduction of the minimum PROFINET send cycle clock from 250 µs to 125 µs (isochronous)
Optimization of data transfer (e.g. by Dynamic Frame Packing - DFP)
By optimized data transfer
more devices can be operated with the same cycle time or
the cycle time can be reduced for the same number of devices
Requirements
The following configuration rules must be taken into account when using the 125 µs send cycle
clocks:
The 125 µs send cycle clock is only available for the SIMOTION D455-2 DP/PN
Configuration only with SCOUT TIA as of V4.5 (SIMOTION in the TIA Portal)
The 125 μs send cycle clock is only supported by the onboard PROFINET interface X150
X150 can only be used as a PROFINET IO controller (not as an I-device)
Only one port can be used on X150; the other two ports must therefore be deactivated in
the interface properties of X150
The following then applies:
The deactivated ports also cannot be used for TCP/IP and UDP communication
No MRP/MRPD media redundancy
Devices that support a send cycle clock of 125 µs must be connected via "one" active
port of X150 (assign device to the controller and configure the Ethernet topology in the
topology view)
For isochronous mode, the clock synchronization must be activated on the controller (sync
master) and on the device (sync slave) (RT class: IRT)
The 125 µs send cycle clock is only supported in conjunction with Servo_fast/IPO_fast;
activate the "Use Servo_fast" option at Isochronous mode in the CPU properties in the TIA
Portal.
In addition to the send cycle clock, the "Enable High Performance" option must be activated
for the sync domain.
Parameter assignment / addressing
6.5 Configuring PROFINET IO
SIMOTION D4x5-2
158 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D4x5-2 and is the answer not in the manual?

Siemens SIMOTION D4x5-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D4x5-2
CategoryControl Unit
LanguageEnglish

Related product manuals