● Λ = flickering LED
●
X = LED state any
9.1.1 SIMOTION D4x5-2 and SINAMICS Integrated displays
LED displays
Every LED can illuminate in yellow, red, or green. In the following table, the color of the LED
is indicated along with the illumination state.
Table 9-1 LED displays
Meaning LED display
RDY RUN STOP SU/PF SF DP DP/
MPI
PN SY/MT OPT
Power-up 1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
Power-up of the D4x5‑2 without
CF
card or with CF card without
valid operating system (possi‐
bly incorrect / missing defective
boot loader).
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
1
(yel‐
low)
Power-up stopped, reason e.g.:
●
incorrect firmware (e.g.
D4x5)
● CBE30‑2 plugged into
D4x5‑2 DP
x 2/1
(yel‐
low)
2/1
(yel‐
low)
2/1
(yel‐
low)
2/1
(yel‐
low)
2/1
(yel‐
low)
2/1
(yel‐
low)
x x x
CF card has begun to boot,
however,
an error has occurred
(faulty firmware).
0.5/1
(red)
0 0 0 0 0 0 0 0 0
D4x5‑2 ready for operation: SI‐
MOTION task system is run‐
ning,
and SINAMICS Integrated
is ready to operate
1
(green)
x x x x x x x x x
Read or write access to CF card Λ
(yel‐
low)
x x x x x x x x x
RUN x 1
(green)
0 0 x x x x x x
Transition from RUN - STOPU x 1
(green)
0 2/1
(yel‐
low)
x x x x x x
Transition from STOPU - RUN x 2/1
(green)
0 1
(yel‐
low)
x x x x x x
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
380 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B