See also
Also refer to the information in Section
General information on SINAMICS firmware update
(Page 370).
7.4.7.4 Replacing the CX32-2
Replacing a module
When used as a spare part, a CX32‑2 behaves like other DRIVE-CLiQ components.
A module replacement is detected automatically as of SINAMICS V4.5.
See Section
Replacing modules in the spare part scenario (Page 114)
Backing up / restoring / deleting SINAMICS NVRAM data (Page 233)
D435-2/D445-2/D455-2 ↔ D425-2 replacement
Drag-and-drop operations can be used to perform a D435-2/D445-2/D455-2 D425-2 module
replacement in HW Config.
Please note that it will not be possible to replace a D435-2/D445-2/D455-2 with a D425-2 if a
CX32-2 has been configured with the address 14 or 15. (A D425-2 does not have DRIVE-CLiQ
ports X104/X105 and therefore does not have addresses 14 and 15.)
Commissioning (software)
7.4 Configuring a CX32-2
SIMOTION D4x5-2
224 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D4x5-2 and is the answer not in the manual?

Siemens SIMOTION D4x5-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D4x5-2
CategoryControl Unit
LanguageEnglish

Related product manuals