Meaning LED display
RDY RUN STOP SU/PF SF DP DP/
MPI
PN SY/MT OPT
DCP flashing
(for interface X120, X127,
X130, X150, X1400)
This function is used to check
the correct assignment to a
module
and its interfaces. DCP
flashing of the module is activa‐
ted in HW Config under "Target
system" > "Ethernet" > "Edit
Ethernet node" > "Browse" but‐
ton > "Flashing" button
x x x x 2/1
(red)
x x x x x
Incompatible hardware; SIMO‐
TION Kernel is no longer oper‐
ating with complete functionali‐
ty on the hardware being used
1
(yel‐
low)
1
(red)
x x x x x x x x
Underlicensing of technology/
option objects
x x x x 0.5/1
(red)
x x x x x
SIMOTION IT service mode /
switch position 8 for 120 mi‐
nutes.
x x x x 0.5/1
(red)
x x x x x
SINAMICS Integrated
Initialization of SINAMICS firm‐
ware
1
(yel‐
low)
x x x x x x x x 0
Component detection via LED
is activated (p0124[0]).
3)
2/1
(green-
yellow
or red-
yellow)
x x x x x x x x x
Commissioning/reset 0.5/1
(green)
x x x x x x x x 0
SINAMICS Integrated is ready
for operation and cyclic
DRIVE‑CLiQ
communication is
taking place
1
(green)
x x x x x x x x x
General SINAMICS Integrated
error (check parameterization/
configuration)
2/1
(red)
x x x x x x x x x
SINAMICS Integrated has not
powered up (SINAMICS firm‐
ware not available / faulty / in‐
correct firmware on CF) or a
fault has occurred in SINAM‐
ICS Integrated
1
(red)
x x x x x x x x x
Read or write access to CF card Λ
(yel‐
low)
x x x x x x x x x
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
382 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B