5.2.5 Layout of modules on several racks
Overview
With the SIMOTION C, a 2-tier layout is possible.
Interface modules
Interface modules are required for the 2-tier layout which route the backplane bus from one
rack to the other. The SIMOTION C is always located on rack 0.
Table 5-3 Interface modules
Interface module Usable for ... Article number
IM 365 SEND Rack 0 6ES7 365-0BA01-0AA0
IM 365 RECEIVE Rack 1
IM 365 interface modules
The two IM 365 interface modules have a fixed connection via a 1-meter long connecting
cable.
The total power consumption of the inserted I/O modules of both racks must not exceed 1.2
A; the power consumption from rack 1 is limited to 800 mA.
Rules
The following rules apply with respect to the layout of the modules on two racks:
The interface module always occupies Slot 3 and is always left of the first signal module.
No more than eight modules may be inserted per rack. These modules are always to the
right of the interface modules.
The number of inserted modules is limited by the permissible power consumption from the
backplane bus. Total power consumption must not exceed 1.2 A (see Technical data table
for each module in the manual
S7-300 Automation System, M7-300 Module Data
).
Configuring and installing
5.2 Configuring an installation using SIMOTION C modules
SIMOTION C
Operating Instructions, 11/2016, A5E33441428B 81

Table of Contents

Other manuals for Siemens SIMOTION

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION and is the answer not in the manual?

Siemens SIMOTION Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION
CategoryControl Unit
LanguageEnglish

Related product manuals