EasyManuals Logo
Home>Siemens>Inverter>SINAMICS G120C

Siemens SINAMICS G120C Function Manual

Siemens SINAMICS G120C
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
3.6 Recommendations for stable operation
The following preconditions must be satisfied to ensure disturbance-free inverter operation
with the extended functions enabled:
Motor and inverter are adequately dimensioned for this application:
The inverter is operated below its current limit.
The rated currents of the motor and inverter must not differ by more than a factor of 5:
Inverter rated current/motor rated current < 5 (r0207[0] / p0305 < 5).
Before commissioning the safety functions, optimally set the closed-loop control:
Carry out motor data identification at standstill.
Carry out a rotating measurement.
Avoid multiple speed overshoots when settling after a setpoint change.
Avoid reversing the motor within less than 2 s.
Description
3.6 Recommendations for stable operation
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
30 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Siemens SINAMICS G120C Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G120C
CategoryInverter
LanguageEnglish

Related product manuals