A.2.7 SSM acceptance test
The two diagrams show the recommended steps to take during the acceptance test. It differs
depending on the settings you have made for SSM:
Diagram 1: The "speed below limit value" checkback signal remains active when the motor
is switched off.
Diagram 2: The "speed below limit value" checkback signal becomes inactive when the
motor is switched off.
The diagrams show the setting "SSM without hysteresis" as an example.
6ZLWFKHGRQ
6SHHG
6HWSRLQW
*UHHQRQ
<HOORZRQ<HOORZIODVKHVVORZO\<HOORZIODVKHV
VORZO\
'LDJQRVWLFV
6SHHGEHORZWKHOLPLW
YDOXH
672DFWLYH
212))
*DWLQJ
'HVHOHFW672
212))
=HURVSHHG
GHWHFWLRQ
6$)(
5'<
W
W
U
U
/('
W
U
S
660
PV
V
Figure A-9 Diagram 1 - acceptance test SSM with active feedback signal when the motor is switched off
Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
398 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD