Configuration
5-297SJ62 Manual
C53000-G1140-C121-1
5.2.5 Transferring Metering Values
The transferring of metered values from the buffer of the device to SCADA or substa-
tion controller may be performed both cyclically and/or by external polling.
In the configuration matrix, click on 2SWLRQV and then on 5HVWRUH0HWHUHG9DO
XHV. A dialog box, which contains a register for editing the individual values for cyclical
transferring will open.
Cyclical Restora-
tion
Here, the user may specify the source of the cyclical trigger for the transfer. Also, the
user may set the time interval and determine whether the metered value buffer should
be deleted after transfer to the SCADA has taken place.
Figure 5-29 Dialog Box to Restore Metered Values and Program Cyclical Restoration
In the current version of DIGSI
®
4, triggering occurs based on the programmed
Absolute time.
5.2.6 Setting of Contact Chatter Blocking
Contact Chatter
Blocking
The contact chatter filter checks whether the number of condition changes at a binary
input exceeds a preset value during a predetermined time interval. If this occurs, the
binary input will be blocked for a certain time, so the event list does not contain a large
number of unnecessary entries. The setting values necessary for this feature may be
LED 5 Pickup G Non-Directional G
Directional G
Pickup by Ground Element
LED 6 Measurement
Failure
Fault ΣI
Fault I Symmetry
Fault V Symmetry
Fault I Rotation
Fault V Rotation
Monitoring Message
LED 7 Not Configured
Table 5-4
Preset Configuration for LED Display
LED Descriptive Text Brief Text Message # Comments