EasyManuals Logo
Home>Siemens>Relays>SIPROTEC 7SJ62

Siemens SIPROTEC 7SJ62 Instruction Manual

Siemens SIPROTEC 7SJ62
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #310 background imageLoading...
Page #310 background image
Functions
6-170 7SJ62 Manual
C53000-G1140-C121-1
The long-term averages of the three phase currents I
x
; the positive sequence com-
ponents I
1
for the three phase currents; and the real power P, reactive power Q, and
apparent power S; in primary values. The period of time for averaging is selectable.
Minimum and maximum values for the above mentioned long-term averages, in-
cluding the date and time they were last updated, in primary values.
Real and reactive energy flow (including direction of flow) in kWh, MWh, or GWh
primary; or in kVArh, MVArh, or GVArh primary.
−Θ/Θ
out
overload protection values for stator and rotor in % of the trip initiating ex-
cessive temperature,
I
Greal
and I
Greactive
real and reactive components of the sensitive ground current de-
tection as secondary quantities in mA.
The measured values are updated at a period of 0.3 s and 1 s.
The minimum and maximum values are listed with the date and time of the latest up-
date. Using binary inputs or a SCADA interface, the maximum and minimum values
can be reset. In addition, the reset can also take place cyclically, beginning with a pre-
selected point in time.
For the long-term averages mentioned above, the length of the time window for aver-
aging and the frequency with which it is updated can be set. The associated minimum
and maximum values can be reset, using binary inputs or by using the integrated con-
trol panel in the DIGSI
®
4 operating program.
Transfer of
Measured Values
Measured values can be retrieved by SCADA, or through DIGSI
®
4.
Set points To recognize extraordinary operational conditions, warning levels can be pro-
grammed. When a programmed limit value is exceeded (or fallen below), a message
is generated that can be masked to both output relays and LEDs. In contrast to the
actual protective functions, such as time-overcurrent protection or overload protection,
this monitoring program may becomes lower.
The following individual limit value levels are configured, when delivered from factory:
Falling below a preset current in any phase
Exceeding a preset maximum average current in Phase A
Exceeding a preset maximum average current in Phase B
Exceeding a preset maximum average current in Phase C
Exceeding a preset maximum average positive sequence current
Exceeding a preset maximum average real power
Exceeding a preset maximum average reactive power
Exceeding a preset maximum average apparent power
Falling below a preset power factor
6.19.3 Waveform Capture
The 7SJ62 relay is equipped with an oscillographic data saving feature. The momen-
tary values for the measurement quantities
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals