Appendix
A-177SJ62 Manual
C53000-G1140-C121-1
A.4 Settings
NOTE:
The following table lists all data which are available in the maximum complement of the device. Depen-
dent on the ordered model, only those data may be present which are valid for the individual version.
Addr. Setting Title Setting Options Default Setting Comments
201 CT Starpoint towards Line
towards Busbar
towards Line CT Starpoint
202 Vnom PRIMARY 0.10..400.00 kV 12.00 kV Rated Primary Voltage
203 Vnom SECONDARY 100..125 V 120 V Rated Secondary Voltage (L-L)
204 CT PRIMARY 10..50000 A 100 A CT Rated Primary Current
205 CT SECONDARY 1A
5A
5A CT Rated Secondary Current
206 Vph / Vdelta 1.00..3.00 1.73 Matching ratio Phase-VT To Open-
Delta-VT
207 CT N / CT Ph 0.010..1.000 1.000 Neutral CT over Phase CT Ratio
208 CT Ns / CT Ph 0.001..5.000 1.000 Neutral CT(sens.) over Phase CT
Ratio
209 PHASE SEQ. A B C
A C B
A B C Phase Sequence
210 TMin TRIP CMD 0.01..32.00 sec 0.15 sec Minimum TRIP Command Duration
211 TMax CLOSE CMD 0.01..32.00 sec 1.00 sec Maximum Close Command Duration
212 BkrClosed I MIN 0.20..5.00 A 0.20 A Closed Breaker Min. Current Thres-
hold
213 VT Connection Van, Vbn, Vcn
Vab, Vbc, VGnd
Van, Vbn, Vcn VT Connection
214 Rated Frequency 50 Hz
60 Hz
60 Hz Rated Frequency
215 Distance Unit km
Miles
Miles Distance measurement unit
302 CHANGE Group A
Group B
Group C
Group D
Binary Input
IEC60870-5-103
Group A Change to Another Setting Group
401 WAVEFORMTRIGGER Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup Waveform Capture
402 WAVEFORM DATA Fault event
Power System fault
Fault event Scope of Waveform Data
403 MAX. LENGTH 0.30..5.00 sec 1.00 sec Max. length of a Waveform Capture
Record
404 PRE. TRIG. TIME 0.05..0.50 sec 0.10 sec Captured Waveform Prior to Trigger
405 POST REC. TIME 0.05..0.50 sec 0.10 sec Captured Waveform after Event
406 BinIn CAPT.TIME 0.10..5.00 sec 0.50 sec Capture Time via Binary Input
1101 V PRIMARY OP. 0.10..400.00 kV 12.00 kV Primary Operating Voltage