Operators Tools
7-8 7SJ62 Manual
C53000-G1140-C121-1
Figure 7-8 DIGSI
®
4 Selection of Trip Log with Faults Listed in the Data Window
Figure 7-9 DIGSI
®
4 Example of Indications for a Fault, Trip Log Window
7.1.1.4 Ground Fault Messages (Ground Fault messages associated with the sensitive ground fault
function)
For devices with sensitive ground fault detection, special ground fault records are
available. Messages are provided if the protection is set for “$ODUP2QO\” in Address
3101, and the ground fault remains long enough for the time delay to expire.
Up to 15 messages can be recorded for the last 3 faults.
All available messages are displayed in table form and explained in the Appendix. In
a specific case, only the applicable messages appear on the display.
From the
Device Front
With a device ready for operation, first press the key. The 0$,10(18 appears.
The first menu item $QQXQFLDWLRQ is marked.
Press the key to enter the $1181&,$7,21 sub-menu (see Figure 7-1).
Select the menu *URXQG)DXOW/RJ using the key, and move to the records with
the key. The *5281')$8/7/2* selection appears.
MENU
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals