6.14 Automatic Reclosing System (79M)
6.14.1 Description of Automatic Reclosing System
General From experience, the majority of faults associated with overhead distribution feeders
are temporary in nature. Therefore, to maximize service availability, it is desirable to
employ a system that will close the circuit breaker shortly after it is tripped. This is ac-
complished in the 7SJ62 relay via the automatic reclosing system.
When using the automatic reclosing system, if the fault still exists after the circuit
breaker has been reclosed, then the protective elements will re-trip the circuit breaker.
Depending on the number of reclosing attempts programmed for the automatic reclos-
ing system (up to nine are possible), the circuit breaker will either be reclosed again,
or will remain open.
The automatic reclosing function is typically utilized only in situations where the occur-
rence of temporary faults is anticipated. Therefore, the automatic reclosing system is
not applied when the 7SJ62 relay is used to protect generators, motors, transformers,
and cables.
The automatic reclosing function can also be initiated by an external protection relay.
For this application, an output contact from the tripping relay must be wired to a binary
input of the 7SJ62 relay. It is also possible to allow the 7SJ62 relay to work in conjunc-
tion with an external reclosing device.
Figure 6-56 shows an example of a timing diagram for a successful second reclosure.
Figure 6-57 shows an example of a timing diagram for two unsuccessful reclosing
shots, with no additional reclosing of the circuit breaker.
Figure 6-56 Timing Diagram for a Second Successful Reclosure
Trip Command
Breaker Status
Dead Time
Reclose Command
Reset Time
Reclosing
Successful
'($'7,0(

'($'7,0(

70D[&/26(&0'
5(6(77,0(
&DQFHOZLWKDQHZ
7ULS&RPPDQG
&\FOH
FRPSOHWHG
52-a
closed
open
(Blocking Time)
$GGU
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals