Functions
6-38 7SJ62 Manual
C53000-G1140-C121-1
6.2.2.6 Information List for Ground Overcurrent Protection
1313 MANUALCLO
SEMODE
50N-2
Instantaneously
50N-1
Instantaneously
51N
Instantaneously
Inactive
50N-2
Instantaneously
Selection of high speed tripping
element when manual closing
feature is used
XXXXX
1314 50N-2 active Always
with 79 active
Always Criteria for operation of 50N-2
element
XXXXX
1330 50N/51N 51N user defined characteristic
curve values
XX
1331 MofPU Res
T/TEp
51N user defined characteristic
curve reset values
X
F# LCD-Text Comment
1761 50(N)/51(N) PU
50(N)/51(N) O/C PICKUP
1791 50(N)/51(N)TRIP
50(N)/51(N) TRIP
F# LCD-Text Comment
1756 50N/51N OFF 50N/51N is OFF
1757 50N/51N BLK 50N/51N is BLOCKED
1758 50N/51N ACT 50N/51N is ACTIVE
1831 50N-2 picked up 50N-2 picked up
1833 50N-2 TRIP 50N-2 TRIP
1834 50N-1 picked up 50N-1 picked up
1836 50N-1 TRIP 50N-1 TRIP
1837 51N picked up 51N picked up
1839 51N TRIP 51N TRIP
1867 51N Disk Pickup 51N Disk emulation picked up
1832 50N-2 TimeOut 50N-2 Time Out
1835 50N-1 TimeOut 50N-1 Time Out
1838 51N TimeOut 51N Time Out
1765 50N/51NPickedup 50N/51N picked up
1853 50N-1 BLOCKED 50N-1 BLOCKED
1854 50N-2 BLOCKED 50N-2 BLOCKED
Addr. LCD-Text Setting Options Default Setting Comments Configuration
Definite Time Only
IEC Curve
ANSI Curve
User Defined Pickup
User def. Reset