Functions
6-1657SJ62 Manual
C53000-G1140-C121-1
6.18.4 Statistical Counters
6.18.4.1 Description
Number of Trips The number of trips initiated by the 7SJ62 is counted, as long as the position of the
circuit breaker is monitored via breaker auxiliary contacts and binary inputs.
Fault Current Furthermore, the fault current in each pole of the circuit breaker is determined for each
trip signal. The fault current is indicated in the fault messages and is added to previ-
ously stored fault current values in the statistic-counters to maintain an accumulation
of fault currents, per pole, experienced by the breaker over time.
Operating hours The operating hours under load are also stored (the current value in at least one phase
is larger than the limit value set under address %NU&ORVHG,0,1). The
counter and memory levels are secured against loss of auxiliary voltage.
6.18.4.2 Setting/Resetting
Setting or resetting of the statistical counters listed above takes place under the menu
item $1181&,$7,21 → 67$7,67,& by overwriting the counter values shown.
6.18.4.3 Information List for the Device
F# LCD-Text Explanation
0051 Device OK Device is Operational and Protecting
0052 ProtActive At Least 1 Protection Funct. is Active
0055 Reset Device Reset Device
0056 Initial Start Initial Start of Device
0067 Resume Resume
0060 Reset LED Reset LED
0110 Event Lost Event lost
0113 Flag Lost Flag Lost
0140 Error Sum Alarm Error with a summary alarm
0160 Alarm Sum Event Alarm Summary Event
0178 I/O-Board error I/O-Board Error
0144 Error 5V Error 5V (power supply)
0145 Error 0V Error 0V (offset monitoring)
0146 Error -5V Error -5V (power supply)
0147 Error PwrSupply Error Power Supply
0177 Fail Battery Battery empty
0070 Settings Calc. Setting calculation is running