Functions
6-657SJ62 Manual
C53000-G1140-C121-1
Non-Directional
Elements
The dynamic pickup values and time delays associated with non-directional overcur-
rent phase protection are set at address block 18.
The dynamic pickup and delay settings for the 50-2 element are set at addresses
 F3,&.83 and  F'(/$< respectively; the dynamic pickup and
delay settings for the 50-1 element are set at addresses  F3,&.83 and
 F'(/$< respectively; and the pickup, time multiplier (for IEC curves), and
time dial (for ANSI curves) settings for the 51 element are set at addresses  F
3,&.83, , and  respectively (F7,0(',$/.
Non-Directional
Ground Elements
The dynamic pickup values and time delays associated with non-directional overcur-
rent ground protection are set at address block 19.
The dynamic pickup and delay settings for the 50N-2 element are set at addresses
 1F3,&.83 and  1F'(/$< respectively; the dynamic pickup
and delay settings for the 50N-1 element are set at addresses  1F3,&.83
and  1F'(/$< respectively; and the pickup, time multiplier (for IEC
curves), and time dial (for ANSI curves) settings for the 51N element are set at ad-
dresses  1F3,&.83, , and  respectively (1F7',$/.
Directional Phase
Elements
The dynamic pickup values and time delays associated with directional overcurrent
phase protection are set at address block 20.
The dynamic pickup and delay settings for the 67-2 element are set at addresses
 F3,&.83 and F'(/$< respectively; the dynamic pickup and
delay settings for the 67-1 element are set at addresses  F3,&.83 and
 F'(/$< respectively; and the pickup, time multiplier (for IEC curves), and
time dial (for ANSI curves) settings for the 67-TOC element are set at addresses 
F72&3,&.83, , and  respectively (F72&7',$/.
Directional Ground
Element
The dynamic pickup values and time delays associated with directional overcurrent
ground protection are set at address block 21.
The dynamic pickup and delay settings for the 67N-2 element are set at addresses
 1F3,&.83 and  1F'(/$< respectively; the dynamic pickup
and delay settings for the 67N-1 element are set at addresses  1F3,&.83
and  1F'(/$< respectively; and the pickup, time multiplier (for IEC
curves), and time dial (for ANSI curves) settings for the 67N-TOC element are set at
addresses 1F72&3,&.83, , and  respectively (1F72&7
',$/.
6.4.2.1 Settings for Dynamic Cold Load Adjustments
In the list below, the setting ranges and default setting values for the pickup currents
are for an equipment with a nominal current rating I
N
= 5 A. For a nominal current rat-
ing I
N
= 1 A, divide the Setting Options values and Default Setting values by 5. Con-
sider the current transformer ratios when setting the equipment with primary values.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals