Functions
6-337SJ62 Manual
C53000-G1140-C121-1
1
) only available with 79 function is enabled
1202 50-2 PICKUP 0.50 ~ 175.00 A 10.00 A Pickup setting of the 50-2
element
XXXXX
1203 50-2 DELAY 0.00 ~ 60.00 sec 0.00 sec Delay setting of the 50-2
element
XXXXX
1204 50-1 PICKUP 0.50 ~ 175.00 A 5.00 A Pickup setting of the 50-1
element
XXXXX
1205 50-1 DELAY 0.00 ~ 60.00 sec 0.50 sec Delay setting of the 50-1
element
XXXXX
1207 51 PICKUP 0.50 ~ 20.00 A 5.00 A Pickup setting of the 51
element
XXXX
1208 51 TIME DIAL 0.05 ~ 3.20 sec 0.50 sec Time multiplier T Ip, IEC and
User Defined Curves
XXX
1209 51 TIME DIAL 0.50 ~ 15.00 5.00 sec Time dial setting, ANSI X
1210 51 Drop-out Instantaneous
Disk Emulation
Disk Emulation Characteristics of 51 dropout X X
1211 51 IEC CURVE Normal Inverse
Very Inverse
Extremely Inverse
Long Inverse
Normal Inverse Characteristic curve (IEC) X
X
X
X
1212 51 ANSI
CURVE
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very Inverse Characteristic curve (ANSI) X
X
X
X
X
X
X
1213 MANUAL
CLOSE
50-2 Instantaneously
50-1 Instantaneously
51 Instantaneously
Inactive
50-2
Instantaneously
Selection of high speed
tripping element when
manual closing feature is
used
XXXXX
1214
50-2 active
1
)
Always
with 79 active
Always Criteria for operation of 50-2
element
XXXXX
1230 51/51N 51 user defined
characteristic curve values
XX
1231 MofPU Res T/
Tp
51 reset user defined curve
values
X
Addr. Setting Title Setting Options Default Setting Comments Configuration
Definite Time Only
IEC Curve
ANSI Curve
User Defined Pickup
User def. Reset
www . ElectricalPartManuals . com