Functions
6-1617SJ62 Manual
C53000-G1140-C121-1
1
) After three unsuccessful restart attempts, the device will go out of service.
2
) Protection and control function are blocked, HMI might be still accessible.
Current Summation
CT Error) Message „)DLOXUHΣ,“
(FNo. 162)
as masked
Current Symmetry
CT Error Message „)DLO,EDODQFH“
(FNo. 163)
as masked
Voltage Symmetry
VT Error Message „)DLO9EDODQFH“
(FNo. 167)
as masked
Voltage Phase
Sequence
External (connections or
power system)
Message „)DLO3K6HT9“
(FNo. 176)
as masked
Current Phase
Sequence
External (connections or
power system)
Message „)DLO3K6HT,“
(FNo. 175)
as masked
Fuse–Failure–
Monitor
External (VTs, fuses, or
control cable)
Message „VT )XVH)DLOXUH“
(FNo. 6575)
as masked
Trip Circuit
Monitoring
External (open trip coil or
blown fuses)
Message „)DLO7ULSFLU“
(FNo. 6865)
as masked
Table 6-6 Summary of the Device Malfunction Responses
Monitoring Possible Cause Malfunction Re-
sponse
Message Output
www . ElectricalPartManuals . com