Installation and Commissioning
8-317SJ62 Manual
C53000-G1140-C121-1
The first time a button is clicked in the Action column to send a message, Password
No. 6 (for hardware test menus) is requested. After correct input of the password, mes-
sages can be individually transmitted. To send a message, click on the Action button
of the corresponding line. The corresponding message is then sent. The message can
be read in the Event Log of the SIPROTEC
®
device and in the SCADA.
The capability of sending further messages remains until the dialog box is closed.
Ending the
Procedure
To end the System Interface Test, click on &ORVH. The device is briefly out of service
while the start-up routine is executed. The dialog box closes.
Note:
When the System Interface Test is terminated, the device changes to the start-up
mode (reboots). All hardware components are returned to the operating conditions de-
termined by the substation settings; however, all message buffers are deleted. Any
data required from the message buffers must therefore be read before the test is
closed.