Configuration
5-4 7SJ62 Manual
C53000-G1140-C121-1
Adr. Setting Setting Options Default Setting Explanation
103 Grp Chge OPTION Disabled
Enabled
Disabled Setting group switching
(A, B, C, D)
104 OSC. FAULT REC. Disabled
Enabled
Disabled Waveform capture
112 Charac. Phase Disabled
Definite Time only
Time Overcurrent Curve IEC
Time Overcurrent Curve ANSI
User Defined Pickup Curve
User def. Reset
Definite Time only Determines if definite-time (50)
and inverse-time (51) elements
are enabled, and the general
characteristics available for 51.
Selection of 51 automatically
enables 50.
113 Charac. Ground Disabled
Definite Time only
Time Overcurrent Curve IEC
Time Overcurrent Curve ANSI
User Defined Pickup Curve
User def. Reset
Definite Time only Determines if definite-time (50N)
and inverse-time (51N) elements
are enabled, and the general
characteristics available for 51N.
Selection of 51N automatically
enables 50N.
115 67/67–TOC Disabled
Definite Time only
Time Overcurrent Curve IEC
Time Overcurrent Curve ANSI
User Defined Pickup Curve
User def. Rese
Definite Time only Determines if directional, phase,
definite-time (67) and inverse-
time (67-TOC) elements are
enabled, and the general charac-
teristics available for 67-TOC.
Selection of 67-TOC automati-
cally enables 67.
116 67N/67N–TOC Disabled
Definite Time only
Time Overcurrent Curve IEC
Time Overcurrent Curve ANSI
User Defined Pickup Curve
User def. Rese
Definite Time only Determines if directional, ground,
definite-time (67N) and inverse-
time (67N-TOC) elements are
enabled, and the general charac-
teristics available for 67N-TOC.
Selection of 67N-TOC automati-
cally enables 67N.
117 Coldload Pickup Disabled
Enabled
Disabled Dynamic cold load setting adjust-
ments
122 InrushRestraint Disabled
Enabled
Disabled Inrush restraint (stabilization) of
phase and ground 50/51/67
131 Sens. Gnd Fault Disabled
Definite Time only
User Defined Pickup Curve
Disabled Sensitive ground fault detection.
Similar to Addresses 112 through
116.
140 46 Disabled
Definite Time only
Time Overcurrent Curve ANSI
Time Overcurrent Curve IEC
Disabled Negative-sequence current pro-
tection. Similar to Addresses 112
through 116.
141 48 Disabled
Enabled
Disabled Starting time monitoring for
motors
142 49 Disabled
Enabled
Disabled Thermal overload protection
143 66 #of Starts Disabled
Enabled
Disabled Start inhibit for motors
150 27/59 Disabled
Enabled
Disabled Voltage protection (under and
overvoltage)
154 81 O/U Disabled
Enabled
Disabled Frequency protection (over and
under-frequency)
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals