Data and command errors
(code 5000 to 8999)
Error code Description and remedy
5107 Calibration charcteristic shift not pos‐
sible
5107 Characteristic cannot be moved due to possibility of range vi‐
olation.
7000 Permitted number range violated 7000 The permitted number range, such as for weight values, was
violated.
7002 Length of ASCII string not plausible 7002 The string header in a specified string variable is not plausible.
7007 Calibration weights / Calibration digits
not plausible
7007 Specifications for calibration weights or digits in data record
DR 3 are incorrect (minimum distance, reversal of incline).
7008 Zeroing or tare parameter not plausi‐
ble
7008 The specifications (data record DR 3) or tare specifications
(data record DR 15) are not plausible.
7009 Standstill range / standstill wait time 7009 Standstill range or standstill wait time are not plausible.
7010 Scale interval / rounding 7010 Resolution or selection for rounding to decimal places is not
plausible.
7011 Filter parameters 7011 Specification of filter parameters is not plausible.
9.5.4 Messages by LEDs on the module
The LEDs on the front of the SIWAREX module signal the following status and error messages.
Item Color Labeling Function
Line 1
H1 red DIAG System fault
H2 Green Ready
H11 yellow
Limit 1 responded
H12 yellow Service mode
H13 yellow
Limit 2 responded
H14 Not used
H15 yellow {E} Empty message
H16 Not used
H17 Green
Standstill triggered
H18 Not used
H19 Green 0 ¼ d zero status
H20 Not used
H21 Max Weighing range exceeded
H22 Not used
H23 Green LC Load cell(s) ready for operation (LED off = load
cells faulty)
H24 Not used
H25 yellow Rx/Tx EIA-RS485 communication active
H26 Not used
H40 Green PRW Status of local 24 V supply
Messages
9.5 Message list
SIWAREX WP321