7.3.4 Defining the calibration weights
Figure 7-4 Quick start step 4a
In step 4 you enter the calibration weights which are to be positioned on the scale during the
calibration. If the scale is not empty and the current contents are known, you can define an
"Calibration weight 0" with the current contents of the scale. With an empty scale, this
parameter remains as 0 kg. "Calibration weight 1" usually defines the first reference point of the
scale characteristic. A further reference point ("Calibration weight 2") can also be set in
addition. This is optional, and may not be necessary depending on the mechanical properties
of the scale.
Note that the interval between the calibration weights must be at least 2% of the nominal load
of the scale. With a 1 000 kg scale, a calibration weight of at least 20 kg must therefore be used.
Commissioning
7.3 5-minute quick start with the operator panel and the Ready-for-Use software
SIWAREX WP321
Operating Instructions, 08/2019, A5E33715669A-AD 41

Table of Contents

Other manuals for Siemens SIWAREX WP321

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WP321 and is the answer not in the manual?

Siemens SIWAREX WP321 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WP321
CategoryAccessories
LanguageEnglish

Related product manuals