Variable Note Type L Rw Default Min. Max.
Hardware ver‐
sion number
ES hardware version num‐
ber (e.g. 03)
UINT 2 r 1 - -
OS version
header
String header UBYTE[2] 2 r 2.2 - -
OS version
(loader) - des‐
ignation
Reference V - Release
B - Test
etc.
STRING[2] 2 r 'V ' - -
OS version
(loader) - des‐
ignation
e.g. version n UINT 2 r 'V ' - -
Reserve Reserve UINT 6 r 0 - -
Reserve 4 0 REAL 4 r 0 - -
8.10 DR 10 load cell parameters
The parameters of the analog load cells must be checked prior to the automatic calibration and
modified if necessary. Only the parameters identified by bold font and asterisk (*) need be
entered.
Procedure
● Check the parameters and modify them as required
● Transfer the data record to the scale
● Adjust the scales
Table 8-6 Assignment of data record 10
Variable Note Type L Rw Default Min. Max.
Data record
number
Contains no. of data record UINT 2 r 10 - -
Length Data record length information UINT 2 r 44 - -
Application Information about which application
the DR belongs to
UINT 2 r 201 - -
Version identifi‐
er
Information on the current data re‐
cord version
UINT 2 r 1 1 65635
Reserve UINT 2 rw 1 1 6
Selection of the
sampling rate
(Page 78)
Parameter code 0: Sampling rate
100 Hz (preferably with line frequen‐
cy of 50 Hz)
Parameter code 1: 120 Hz (prefera‐
bly with line frequency of 60 Hz)
Parameter code 2: 600 Hz for fast
measurements
UINT 2 rw 0 0 1
Number of sup‐
port points
(Page 79)
1)
Number of support points UINT 2 rw 0 0 8
Reserve UINT 2 rw 0 0 0
Scale parameters and functions
8.10 DR 10 load cell parameters
SIWAREX WP321
Operating Instructions, 08/2019, A5E33715669A-AD 77