Make sure that the motor stops before autotuning, otherwise, autotuning cannot
be performed.
z Autotuning is only enabled when the inverter is in keypad control mode.
(F0-04=0)
z If overcurrent or overvoltage trips in the process of autotuning,
acceleration/deceleration time 1 can be adjusted (F0-09 and F0-10)
appropriately.
z To ensure a smooth autotuning, set all motor parameters as per the values listed
on motor nameplate correctly:
F1-00: Motor model
F1-01: Motor rated power
F1-02: Motor rated voltage
F1-03: Motor rated current
F1-04: Motor rated frequency
F1-05: Motor rated speed
F1-06: Motor wiring method
F1-07: Motor rated power factor
Configure the inverter with an applicable Y-series motor, and the defaults of
inverter can meet most of needs.
z To ensure control performance, the motor and the inverter should match in
terms of the power rating. Usually the power rating of motor is only allowed to
be one level lower than that of the inverter.
z After autotuning is over normally, the setting value of F1-08~F1-13 will be
updated and autosaved.
z When F0-28=1 reset the default, the parameters of F1-00~F1-13 remains
unchanged.
8.3 Autotuning Procedure
z In parameter setting status, set F0-04=0, and make motor offload.
z Set all motor parameters as per the values listed on nameplate correctly:
F1-00: Motor model
F1-01: Motor rated power
F1-02: Motor rated voltage
F1-03: Motor rated current
F1-04: Motor rated frequency
F1-05: Motor rated speed
F1-06: Motor wiring method
F1-07: Motor rated power factor