User Manual
EM303A General Purpose Inverter
53
6.2.4 Group F3: Preset Speed Operation Parameters
No. Function Range Unit Default Type
F3-00 Preset Speed 1 0.00~Fmax/0.0~Fmax Hz 0.00 ●
F3-01 Preset Speed 2 0.00~Fmax/0.0~Fmax Hz 5.00 ●
F3-02 Preset Speed 3 0.00~Fmax/0.0~Fmax Hz 10.00 ●
F3-03 Preset Speed 4 0.00~Fmax/0.0~Fmax Hz 15.00 ●
F3-04 Preset Speed 5 0.00~Fmax/0.0~Fmax Hz 20.00 ●
F3-05 Preset Speed 6 0.00~Fmax/0.0~Fmax Hz 25.00 ●
F3-06 Preset Speed 7 0.00~Fmax/0.0~Fmax Hz 30.00 ●
F3-07 Preset Speed 8 0.00~Fmax/0.0~Fmax Hz 35.00 ●
F3-08 Preset Speed 9 0.00~Fmax/0.0~Fmax Hz 40.00 ●
F3-09 Preset Speed 10 0.00~Fmax/0.0~Fmax Hz 45.00 ●
F3-10 Preset Speed 11 0.00~Fmax/0.0~Fmax Hz 50.00 ●
F3-11 Preset Speed 12 0.00~Fmax/0.0~Fmax Hz 50.00 ●
F3-12 Preset Speed 13 0.00~Fmax/0.0~Fmax Hz 50.00 ●
F3-13 Preset Speed 14 0.00~Fmax/0.0~Fmax Hz 50.00 ●
F3-14 Preset Speed 15 0.00~Fmax/0.0~Fmax Hz 50.00 ●
F3-15 Acceleration Time 2 0.00~600.00 S/min 15.00 ●
F3-16 Deceleration Time 2 0.00~600.00 S/min 15.00 ●
F3-17 Acceleration Time 3 0.00~600.00 S/min 15.00 ●
F3-18 Deceleration Time 3 0.00~600.00 S/min 15.00 ●
F3-19 Acceleration Time 4 0.00~600.00 S/min 15.00 ●
F3-20 Deceleration Time 4 0.00~600.00 S/min 15.00 ●
F3-21
Acceleration/Deceleration
Time Unit
0: S
1: min
0 〇
F3-22
DC Brake Propotion at
Start
0.00~30.00 , 30.01~150.00 % 35.00 〇
F3-23 DC Brake Time at Start 0.00~30.00 S 0.00 〇
F3-24
DC Brake Start
Frequency at Stop
0.10~60.00/0.1~60.0 Hz 2.00 〇
F3-25
DC Brake Propotion at
Stop
0.00~30.00, 30.01~150.00 % 35.00 〇
F3-26 DC Brake Waiting Time 0.00~30.00 S 0.00 〇
F3-27 DC Brake Time at Stop 0.00~30.00 S 0.00 〇
F3-28
Lower Limit Frequency
Control
0: Run as per Lower Limit
Frequency
1: Run at zero speed after lower
limit frequency operation time is up.
0 〇
F3-29
Lower Limit Frequency
Running Time
0.00~600.00 S 60.00 〇
F3-30
Open Loop Slip
Compensation
0.00~200.00 % 0.00 ●
F3-31 Parameter Copy
0: No Copy
1: Upload Parameter (From Inverter
to Keypad)
2:Download Parameter (From
Keypad to Inverter)
0 〇