AnnexeI-5.Congurationnavigationscreen
1
SETUP
2
VOLT. LEVELS
3
FREQ. LEVELS
4
PWR. LEVELS
5
TIMERS VALUE
6
I-O
7
COMM
(10)
8
DATE/TIME
NETWORK 4NBL OV. U I 115% O V. F I 105% OV.P I 0000 kVA 1FT 0003 SEC IN 1 --- NO DHCP NO (9) YEAR
AUTOCONF NO (7) OV. U HYS I 110% OV. F HYS I 103% OV.P HYS I 0000 kVA 1RT 0180 SEC IN 2 --- NO IP 1-2 192.168.
(9)
MONTH
NEUTRAL AUTO UND. U I 085% UND. F I 095% OV.P I I 0000 kVA 2FT 0003 SEC IN 3 --- NO IP 3-4 .002.001 DAY
ROT PH. --- UND. U HYS I 095% UND. F HYS I 097% OV.P HYS I I 0000 kVA 2RT 0005 SEC (2) IN 4 --- NO GAT1-2 000.000.
(9)
HOUR
NOM. VOLT 400 V UNB. U I 00% O V. F I I 105% 2AT 0005 SEC (1) IN 5 --- NO GAT3-4 .000.000 MINUTE
NOM. FREQ 50 Hz UNB. U HYS I 00% OV. F HYS I I 103% 2CT 0180 SEC (1) IN 6 --- NO MSK1-2 255.255.
(9)
SECOND
APP M-G OV. U I I 115% UND. F I I 095% 2ST 0030 SEC (1) IN 7 --- NO (8) MSK3-4 .255.000
PRIO TON NO (1) OV. U HYS I I 110% UND. F HYS I I 097% ODT 0003 SEC IN 8 --- NO (8) ADDRESS 005
PRIO EON NO (3) UND. U I I 085% TOT UNL (1) IN 9 --- NO (8) BDRATE 9600
PRIO NET 1 (2) UND. U HYS I I 095% TOT 0010 SEC (1) IN10 --- NO (8) STOP BIT 1
RETRANS NO UNB. U I I 00% T3T 0000 SEC (1) IN11 --- NO (8) PARITY NONE
CT PRI 100 UNB. U HYS I I 00% TFT UNL (1) IN12 --- NO (8)
CT SEC 5 TFT 0600 SEC (1) IN13 --- NO (8)
S1=SW2 NO E1T 0005 SEC (3) IN14 --- NO (8)
BACKLGHT INT E2T UNL (3) OUT 1 POP NO
CODE P 1000 E2T 0010 SEC (3) OUT 2 --- NO (8)
CODE E 0000 E3T 0005 SEC (3) OUT 3 --- NO (8)
BACKUP SAVE E5T 0005 SEC (4) OUT 4 --- NO (8)
E6T LIM (4) OUT 5 --- NO (8)
E6T 0600 SEC (4) OUT 6 --- NO (8)
E7T 0005 SEC (4) OUT 7 --- NO (8)
LST 0004 SEC (5) OUT 8 --- NO (8)
EET 0168 H (6) OUT 9 --- NO (8)
EDT 1800 SEC (6)
(1) When "APP" is set to "M-G"
(2) When "APP" is set to "M-M"
(3) When one of the I/P is set to "EON"
(4) When one of the I/P is set to "EOF"
(5) When one of the O/P is set to "LSC"
(6) When one of the O/P is set to "EES"
(7) If the product is in manual mode
(8) With optional I/O modules
(9) With Ethernet module
(10) Only if a communication module is used
Setup by Auto Conguration
(Volts, Hz, Neutral pos., Ph rotation)
Press 5s
Go To
1
SETUP
Scroll to
AUTOCONF
Enter code 1000
Set to
YES
Press 60 ms
LEDs ash
Save : press 5s
Note: Source
I
or source
II
must be
available to set by Auto Conguration.