H9 ASD Installation and Operation Manual 191
Adding Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 (2-Wire)
6 — RS485 (4-Wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (Terminal Board)
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the commanded frequency.
If Setting (F729) is selected, the % value entered at parameter F729 is used as
the multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Setting (F729)
5 — RX2 Option (AI1)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F660 F661