114 RT-SVP04F-EN
System Testing & Troubleshooting
OA Damper Pos 0% Exhaust Damper: 0% Used With: All units; OA Damper
Pos (Fresh Air) shown if 100%
Economizer* or 25% Motorized OA
Damper installed
Exhaust (Damper) shown only if
Power Exhaust or Return Fan with
Statitrac is installed
Exhaust Fan shown only if Power
Exhaust (no Return Fan) is installed
(with or without Statitrac)
Possible Values: OA Damper: 0 to
100% (Economizer installed) or 0-
25% (Motorized OA Damper
installed); Exhaust Damper= 0-
100%; Exhaust fan= OFF, ON
Exhaust Fan: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Ventilation Override Module Output Relay Used With: All Units when VOM is
installed
Factory Presets:
OFF
Possible Values: ON, OFF
OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed.
VCM Preheater State OFF Used With: All Units when VCM is
installed
Factory Presets:
OFF
Possible Values: ON, OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed.
GBAS 0-5 VDC Module Relay Outputs Used With: All Units when GBAS 0-
5 VDC is installed
Factory Presets: OFF
Possible Values: 1, 2, 3, 4, 5 =
ON, OFF
#1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
GBAS 0-10 VDC Module Relay Outputs Used With: All Units when GBAS 0-
10 VDC is installed
Possible Values: OFF, ON
#1 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)