Parameter Details
12
12.2 A: Initialization Parameters
YASKAWA SIEPC71061753C GA500 Technical Manual 483
12.2 A: Initialization Parameters
A parameters [Initialization Parameters] set the operating environment and operating conditions for the drive.
◆ A1: Initialization
A1 parameters set the operating environment and operating conditions for the drive. For example, these
parameters set the keypad language, the control method, and the parameter access level for the drive.
■ A1-00: Language Selection
No.
(Hex.)
Name Description
Default
(Range)
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0
(0 - 12)
Note:
• This parameter is only available when you use an LCD keypad or a Bluetooth LCD Keypad.
• When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
■ A1-01: Access Level Selection
No.
(Hex.)
Name Description
Default
(Range)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will
display, and which parameters the user can set.
2
(0 - 3)
0 : Operation Only
Access to A1-00, A1-01, A1-04 [Password], and the U Monitors.
1 : User Parameters
Access to A1-00, A1-01, A1-04, and A2-01 to A2-32 [User Parameters 1 to 32].
2 : Advanced Level
Access to all parameters, but not Expert Mode parameters.
3 : Expert Level
Access to all parameters including Expert Mode parameters.
Table 12.1 shows which keypad screens are available for each A1-01 settings.