User Constant Tables
5-25
Option Constants: F
Communications Option Cards: F6
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
F6-01
Operation selec-
tion after commu-
nications error
Set the stopping method for com-
munications errors.
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A 3A2H
F6-02
Input level of
external error
from Communica-
tions Option Card
0: Always detect
1: Detect during operation
0 or 1 0 No A 3A3H
F6-03
Stopping method
for external error
from Communica-
tions Option Card
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A 3A4H
F6-05
Current monitor
unit selection
Sets the unit of current monitor
0: Ampere
1: 100%/8192
0 or 1 1 No A 3A6H
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for YASKAWA Varispeed E7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed E7 and is the answer not in the manual?

YASKAWA Varispeed E7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed E7
CategoryDC Drives
LanguageEnglish

Related product manuals