204 ACH580 E-Clipse bypass and packaged drive user manual
Technical data
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
Disconnect
Switch
UL (NEMA)
Type
1 and 12
Disconnect
Switch
UL (NEMA)
Type 3R
Motor
Terminals
UL (NEMA)
Type 1
and 2
Motor
Terminals
UL (NEMA)
Type 3R
Ground
Lugs
UL
(NEMA)
Type 1
and 2
Ground
Lugs
UL
(NEMA)
Type 3R
AHP
575 Volts
2
ACH580-BxR-02A7-6 2.7 2 R2
#12
62 in-lbs
#12
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#6
11-13 in lbs
#6
11-13 in lbs
#4
35 in-lbs
#4
35 in-lbs
ACH580-BxR-03A9-6 3.9 3 R2
ACH580-BxR-06A1-6 6.1 5 R2
ACH580-BxR-09A0-6 9 7.5 R2
ACH580-BxR-011A-6 11 10 R2
ACH580-BxR-017A-6 17 15 R2
#10
62 in-lbs
#10
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACH580-BxR-022A-6 22 20 R3
#1
35 in-lbs
#1
35 in-lbs
#2
50 in-lbs
ACH580-BxR-027A-6 27 25 R3
#4
55 in-lbs
#4
55 in-lbs
ACH580-BxR-032A-6 32 30 R3
#6
62 in-lbs
ACH580-BxR-041A-6 41 40 R5
Consult
factory
#3
55 in-lbs
Consult
factory
Consult
factory
Consult
factory
ACH580-BxR-052A-6
3
52 50 R5
#2
62 in-lbs
#2
55 in-lbs
#2/0
110 in-lbs
ACH580-BxR-062A-6 62 60 R5
#1
62 in-lbs
#1
275 in-lbs
ACH580-BxR-077A-6 77 75 R5
#1/0
62 in-lbs
#1/0
275 in-lbs
3 x #3/0
250 in-lbs
ACH580-BxR-099A-6 99 100 R7
#3/0
124 in-lbs
#3/0
275 in-lbs
#2/0
71 in-lbs
ACH580-BxR-125A-6 125 125 R7
250
MCM
124 in-lbs
250 MCM
275 in-lbs
300 MCM
301 in-lbs
ACH580-BxR-144A-6 144 150 R8
300 MCM
275 in-lbs
1) “BxR” represents both BCR and BDR.
2) BCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) BCR supports Delta network configuration.