Actual signals and parameters
113
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
3107 AR AI<MIN
Activates/deactivates the automatic reset for AI<MIN (analog input signal
under the allowed minimum level) fault AI1 LOSS (code: F0007).
Automatically resets the fault after the delay set by parameter 3103 DELAY
TIME.
0 = DISABLE
0 = DISABLE
Inactive
1 = ENABLE
Active
WARNING! The drive may restart even after a long stop if the
analog input signal is restored. Ensure that the use of this feature
will not cause danger.
3108 AR EXTERNAL FLT
Activates/deactivates the automatic reset for faults EXT FAULT 1/EXT FAULT
2 (code: F0014/F0015). Automatically resets the fault after the delay set by
parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE
Inactive
1 = ENABLE
Active

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 series and is the answer not in the manual?

ABB ACS150 series Specifications

General IconGeneral
Power Range0.37 to 4 kW
Frequency Range0 to 500 Hz
Protection ClassIP20
Overload Capacity150% for 60 seconds
Braking ChopperBuilt-in
Control MethodScalar control
Supply Voltage200-240 V (1-phase), 200-480 V (3-phase)
EMC FilterBuilt-in
Input Voltage200-240 V (1-phase), 200-480 V (3-phase)
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit
Communication OptionsModbus RTU
Voltage Range200 to 240 V (1-phase), 380 to 480 V (3-phase)

Related product manuals