83
Actual signals and parameters
Parameters in the Short parameter mode
No.
Name/Value
Description
Def
22 ACCEL/DECEL
Acceleration and deceleration times
2202 ACCELER TIME 1
Defines the acceleration time 1, that is the time required for the speed to
change from zero to the speed defined by parameter 2008 MAXIMUM FREQ.
- If the speed reference increases faster than the set acceleration rate, the
motor speed follows the acceleration rate.
- If the speed reference increases slower than the set acceleration rate, the
motor speed follows the reference signal.
- If the acceleration time is set too short, the drive automatically prolongs the
acceleration in order not to exceed the drive operating limits.
5.0 s
0.01800.0 s
Time
2203 DECELER TIME 1
Defines the deceleration time 1, that is the time required for the speed to
change from the value defined by parameter 2008 MAXIMUM FREQ to zero.
- If the speed reference decreases slower than the set deceleration rate, the
motor speed follows the reference signal.
- If the reference changes faster than the set deceleration rate, the motor
speed follows the deceleration rate.
- If the deceleration time is set too short, the drive automatically prolongs the
deceleration in order not to exceed drive operating limits.
If a short deceleration time is needed for a high inertia application, the drive
should be equipped a brake resistor.
5.0 s
0.01800.0 s
Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 series and is the answer not in the manual?

ABB ACS150 series Specifications

General IconGeneral
Power Range0.37 to 4 kW
Frequency Range0 to 500 Hz
Protection ClassIP20
Overload Capacity150% for 60 seconds
Braking ChopperBuilt-in
Control MethodScalar control
Supply Voltage200-240 V (1-phase), 200-480 V (3-phase)
EMC FilterBuilt-in
Input Voltage200-240 V (1-phase), 200-480 V (3-phase)
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit
Communication OptionsModbus RTU
Voltage Range200 to 240 V (1-phase), 380 to 480 V (3-phase)