Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated
indoor controlled environment.
Op
er
ation
installed for stationary use
St
o
ra
g
e
in the protective package
T
r
an
s
port
a
tion
in the protective package
Installation site altitude
0 to 2000 m (6600 ft) above
sea level
(above 1000 m [3300 ft], see
section Derating on page
138)
-10 to +50 °C (14 to 122 °F).
No frost allowed. See section
Derating on page 138.
-40 to +70 °C ±2%
(-40 to +158 °F) ±2%
-40 to +70 °C
(-40 to +158 °F)
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
According to IEC 60721-3-3,
chemical gases: Class 3C2
solid particles: Class 3S2.
Note: The drive must be
installed in clean air
according to enclosure
classification.
Note: Cooling air must be
clean, free from corrosive
materials and electrically
conductive dust.
According to IEC 60721-3-1,
chemical gases: Class 1C2
solid particles: Class 1S2
According to IEC 60721-3-2,
chemical gases: Class 2C2
solid particles: Class 2S2
Sinusoidal vibration
(IEC 60721-3-3)
Tested according to
IEC 60721-3-3, mechanical
conditions: Class 3M4
2…9 Hz, 3.0 mm (0.12 in)
9…200 Hz, 10 m/s
2
(33 ft/s
2
)
Shock
(IEC 60068-2-27, ISTA 1A)
Not allowed during operation
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
),
11 ms.
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
),
11 ms.
Materials
Drive enclosure • PC/ABS 2 mm, PC+10%GF 2.5…3 mm and PA66+25%GF 1.5 mm, all in color
NCS 1502-Y (RAL 9002 / PMS 420 C)
• hot-dip zinc coated steel sheet 1.5 mm, thickness of coating 20 micrometers
• extruded aluminium AlSi.
Package Corrugated cardboard.