Actual signals and parameters
Parameters in the Short parameter mode
Defines the nominal motor voltage. Must be equal to the value on the motor
rating plate. The drive cannot supply the motor with a voltage greater than
the input power voltage.
Note that the output voltage is not limited by the nominal motor voltage but
increased linearly up to the value of the input voltage
Output voltage
Input voltage
9905
Output frequency
9907
WARNING! Never connect a motor to a drive which is connected to power
line with voltage level higher than the rated motor voltage.
200 V
E units:
200 V
230 V
U units:
230 V
400 V
E units:
400 V
460 V
U units:
460 V
200 V E units/
230 U units:
100...300 V
400 V E units /
460 V U units:
230...690 V
Voltage.
Note: The stress on the motor insulations is always dependent on the drive
supply voltage. This also applies to the case where the motor voltage rating
is lower than the rating of the drive and the supply of the drive.
Defines the nominal motor current. Must be equal to the value on the motor
rating plate.
Defines the nominal motor frequency, that is the frequency at which the
output voltage equals the motor nominal voltage:
Field weakening point = Nom. frequency · Supply voltage / Mot nom. voltage
Fault history (read-only)
Fault code of the latest fault. See chapter Fault tracing on page 127 for the
codes. 0 = fault history is clear (on panel display = NO RECORD).
Defines the maximum value for external reference REF1. Corresponds to
maximum mA/(V) signal for analog input AI1.
REF (Hz)
1105
(MAX)
0
AI1 signal (%)
1301
100%
(20 mA / 10 V)