137
Technical data
Technical data
What this chapter contains
The chapter contains the technical specifications of the drive, for example, the
ratings, sizes and technical requirements as well as provisions for fulfilling the
requirements for CE and other marks.
Ratings
Current and power
The current and power ratings are given below. The symbols are described below
the table.
T
y
p
e
ACS150-
x =
E/U
1)
Inpu
t
Outpu
t
Frame
size
I
1N
A
I
1N
(480 V)
A
I
2N
A
I
2,1min/10min
A
I
2max
A
P
N
k
W
hp
1-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2
6.1
-
2.4
3
.
6
4.2
0.37
0.5
R0
01x-04A7-2
11.4
-
4.7
7
.1
8.2
0.75
1
R1
01x-06A7-2
16.1
-
6.7
10.1
11.7
1
.1
1.5
R1
01x-07A5-2
16.8
-
7.5
11.3
13.1
1
.5
2
R2
01x-09A8-2
21.0
-
9.8
14.7
17.2
2
.2
3
R2
3-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
03x-02A4-2
4.3
-
2.4
3
.
6
4.2
0.37
0.5
R0
03x-03A5-2
6.1
-
3.5
5
.
3
6.1
0.55
0.75
R0
03x-04A7-2
7.6
-
4.7
7
.
1
8.2
0.75
1
R1
03x-06A7-2
11.8
-
6.7
10.1
11.7
1
.1
1.5
R1
03x-07A5-2
12.0
-
7.5
11.3
13.1
1
.5
2
R1
03x-09A8-2
14.3
-
9.8
14.7
17.2
2
.2
3
R2
3-phase U
N
= 380…480 V (380, 400, 415, 440, 460, 480 V)
03x-01A2-4
2.2
1
.
8
1.2
1
.
8
2.1
0.37
0.5
R0
03x-01A9-4
3.6
3
.
0
1.9
2
.
9
3.3
0.55
0.75
R0
03x-02A4-4
4.1
3
.
4
2.4
3
.
6
4.2
0.75
1
R1
03x-03A3-4
6.0
5
.
0
3.3
5
.
0
5.8
1.1
1
.5
R1
03x-04A1-4
6.9
5
.
8
4.1
6
.
2
7.2
1.5
2
R1
03x-05A6-4
9.6
8
.
0
5.6
8
.
4
9.8
2.2
3
R1
03x-07A3-4
11.6
9
.7
7.3
11.0
12.8
3
4
R1
03x-08A8-4
13.6
11
.
3
8.8
13.2
15.4
4
5
R1
00353783.xls
J
1)
E = EMC filter connected (metal EMC filter screw installed),
U = EMC filter disconnected (plastic EMC filter screw installed), US parametrization.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 series and is the answer not in the manual?

ABB ACS150 series Specifications

General IconGeneral
Power Range0.37 to 4 kW
Frequency Range0 to 500 Hz
Protection ClassIP20
Overload Capacity150% for 60 seconds
Braking ChopperBuilt-in
Control MethodScalar control
Supply Voltage200-240 V (1-phase), 200-480 V (3-phase)
EMC FilterBuilt-in
Input Voltage200-240 V (1-phase), 200-480 V (3-phase)
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit
Communication OptionsModbus RTU
Voltage Range200 to 240 V (1-phase), 380 to 480 V (3-phase)