Actual signals and parameters
112
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
3023 WIRING FAULT
Selects how the drive reacts when incorrect input power and motor cable
connection is detected (that is the input power cable is connected to the
motor connection of the drive).
Note: Disabling wiring fault (ground fault) may void the warranty.
1 = ENABLE
0 = DISABLE
No action
1 = ENABLE
The drive trips on fault OUTP WIRING (code F0035).
31 AUTOMATIC RESET
Automatic fault reset. Automatic resets are possible only for certain fault
types and when the automatic reset function is activated for that fault type.
3101 NR OF TRIALS
Defines the number of automatic fault resets the drive performs within the
time defined by parameter 3102 TRIAL TIME.
If the number of automatic resets exceeds the set number (within the trial
time), the drive prevents additional automatic resets and remains stopped.
The drive must be reset from the control panel or from a source selected by
parameter 1604 FAULT RESET SEL.
Example: Three faults have occurred during the trial time defined by
parameter 3102 TRIAL TIME. Last fault is reset only if the number defined
by parameter 3101 NR OF TRIALS is 3 or more.
Trial time
t x = Automatic reset
X X X
0
0…5
Number of the automatic resets
3102 TRIAL TIME
Defines the time for the automatic fault reset function. See parameter 3101
NR OF TRIALS.
30.0 s
1.0…600.0 s
Time
3103 DELAY TIME
Defines the time that the drive waits after a fault before attempting an
automatic reset. See parameter 3101 NR OF TRIALS. If delay time is set to
zero, the drive resets immediately.
0.0 s
0.0…120.0 s
Time
3104 AR OVERCURRENT
Activates/deactivates the automatic reset for the overcurrent fault.
Automatically resets fault OVERCURRENT (code: F0001) after the delay set
by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE
Inactive
1 = ENABLE
Active
3105 AR OVERVOLTAGE
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault. Automatically resets fault DC OVERVOLT (code: F0002)
after the delay set by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE
Inactive
1 = ENABLE
Active
3106 AR UNDERVOLTAGE
Activates/deactivates the automatic reset for the intermediate link
undervoltage fault. Automatically resets fault DC UNDERVOLT (code:
F0006) after the delay set by parameter 3103 DELAY TIME.
0 = DISABLE
0 = DISABLE
Inactive
1 = ENABLE
Active