Actual signals and parameters
115
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
0, x…x
Parameter index in group 01 OPERATING DATA. For example, 102 = 0102
SPEED.
0 = not selected.
3202 SUPERV 1 LIM LO
Defines the low limit for the first supervised signal selected by parameter
3201 SUPERV 1 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter 3201 SUPERV 1 PARAM setting.
-
3203 SUPERV 1 LIM HI
Defines the high limit for the first supervised signal selected by parameter
3201 SUPERV 1 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter 3201 SUPERV 1 PARAM setting.
-
3204 SUPERV 2 PARAM
Selects the second supervised signal. Supervision limits are defined by
parameters 3205 SUPERV 2 LIM LO and 3206 SUPERV 2 LIM HI. See
parameter 3201 SUPERV 1 PARAM.
104
x…x
Parameter index in group 01 OPERATING DATA. For example, 102 = 0102
SPEED.
3205 SUPERV 2 LIM LO
Defines the low limit for the second supervised signal selected by parameter
3204 SUPERV 2 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter 3204 SUPERV 2 PARAM setting.
-
3206 SUPERV 2 LIM HI
Defines the high limit for the second supervised signal selected by parameter
3204 SUPERV 2 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter 3204 SUPERV 2 PARAM setting.
-
3207 SUPERV 3 PARAM
Selects the third supervised signal. Supervision limits are defined by
parameters 3208 SUPERV 3 LIM LO and 3209 SUPERV 3 LIM HI. See
parameter 3201 SUPERV 1 PARAM.
105
x…x
Parameter index in group 01 OPERATING DATA. For example, 102 = 0102
SPEED.
3208 SUPERV 3 LIM LO
Defines the low limit for the third supervised signal selected by parameter
3207 SUPERV 3 PARAM. Supervision wakes up if the value is below the
limit.
-
x…x
Setting range depends on parameter 3207 SUPERV 3 PARAM setting.
-
3209 SUPERV 3 LIM HI
Defines the high limit for the third supervised signal selected by parameter
3207 SUPERV 3 PARAM. Supervision wakes up if the value is above the
limit.
-
x…x
Setting range depends on parameter 3207 SUPERV 3 PARAM setting.
-
33 INFORMATION
Firmware package version, test date etc.
3301 FIRMWARE
Displays the version of the firmware package.
0000…FFFF (hex)
For example, 135B hex
3302 LOADING PACKAGE
Displays the version of the loading package.
Type
dependent
200120FF hex
2021 hex = ACS150-0nE-
2022 hex = ACS150-0nU-
3303 TEST DATE
Displays the test date.
00.00
Date value in format YY.WW (year, week)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 series and is the answer not in the manual?

ABB ACS150 series Specifications

General IconGeneral
Power Range0.37 to 4 kW
Frequency Range0 to 500 Hz
Protection ClassIP20
Overload Capacity150% for 60 seconds
Braking ChopperBuilt-in
Control MethodScalar control
Supply Voltage200-240 V (1-phase), 200-480 V (3-phase)
EMC FilterBuilt-in
Input Voltage200-240 V (1-phase), 200-480 V (3-phase)
Protection FeaturesOvervoltage, undervoltage, overcurrent, short-circuit
Communication OptionsModbus RTU
Voltage Range200 to 240 V (1-phase), 380 to 480 V (3-phase)