Parameters 109
01.14 Output power Measured output power in kW. The unit is selected by
parameter 96.16 Unit selection. The filter time constant
can be adjusted by parameter 46.14 Filter time power.
-
-32768.00… 32767.00
kW
Output power. See par.
46.04
01.15 Output power % of
motor nom
Measured output power in % of nominal motor power. -
-300.00… 300.00% Output power. 10 = 1%
01.17 Motor shaft power Estimated mechanical power at motor shaft in kW or hp.
Parameter 96.16 Unit selection defines the unit. The filter
time constant can be adjusted by parameter 46.14 Filter
time power.
-
-32768.00… 32767.00
kW or hp
Motor shaft power. See par.
46.04
01.18 Inverter GWh counter Amount of energy that has passed through the drive (in
either direction) in full gigawatt-hours. The minimum value
is zero.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.19 Inverter MWh counter Amount of energy that has passed through the drive (in
either direction) in full megawatt-hours. Whenever the
counter rolls over, 01.18 Inverter GWh counter is
incremented. The minimum value is zero.
-
0…1000 MWh Energy in MWh. 1 = 1 MWh
01.20 Inverter kWh counter Amount of energy that has passed through the drive (in
either direction) in full kilowatt-hours. Whenever the
counter rolls over, 01.19 Inverter MWh counter is
incremented. The minimum value is zero.
-
0…1000 kWh Energy in kWh. 10 = 1 kWh
01.24 Flux actual % Used flux reference in percent of nominal flux of motor. -
0…200% Flux reference. 1 = 1%
01.30 Nominal torque scale Nominal torque in N•m which corresponds to 100%.
Note: This parameter is copied from parameter 99.12
Motor nominal torque if given. Otherwise the
value is calculated from other motor data.
0
0.000…4000000
N·morlb·ft
Nominal torque. 1 = 100 unit
01.50 Current hour kWh Current hour energy consumption. This is the energy of
the last 60 minutes (not necessarily continuous) the drive
has been running, not the energy of a calendar hour. The
value is set to the value before the power cycle when the
drive is again up and running.
- / -
0.00…1000000.00
kWh
Energy. 1 = 1 kWh
01.51 Previous hour kWh Previous hour energy consumption. The value Current
hour kWh is stored here when its values has been
cumulated for 60 minutes. The value is set to the value
before the power cycle when the drive is again up and
running.
-
0.00…1000000.00
kWh
Energy. 1 = 1 kWh
No. Name/Value Description Default
FbEq 16