01.30 Nominal torque scale Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter 96.16 Unit selection
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is
calculated from other motor data.
0.000
N·m or lb·ft
0.000...4000000.000
N·m or lb·ft
Nominal torque. 1 = 100 unit
01.31 Ambient temperature Measured temperature of incoming cooling air. The unit is
selected by parameter 96.16 Unit selection.
-
-40…120 °C or °F Cooling air temperature. 1 = 1°
01.32 Inverter GWh
regenerating
Amount of energy that has passed through the drive
(towards the supply) in full gigawatt-hours. The minimum
value is zero.
-
0…32767 GWh Motoring energy in GWh. 1 = 1 GWh
01.33 Inverter MWh
regenerating
Amount of energy that has passed through the drive
(towards the supply) in full megawatt-hours. Whenever the
counter rolls over, 01.32 Inverter GWh regenerating is
incremented.The minimum value is zero.
-
0…1000 MWh Motoring energy in MWh. 1 = 1 MWh
01.34 Inverter kWh
regenerating
Amount of energy that has passed through the drive
(towards the supply) in full kilowatt-hours. Whenever the
counter rolls over, 01.33 Inverter MWh regenerating is
incremented.The minimum value is zero.
-
0…1000 kWh Motoring energy in kWh. 10 = 1 kWh
01.35 Mot - regen energy
GWh
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full gigawatt-
hours.
-
-32768…32767 GWh Motoring energy in GWh. 1 = 1 GWh
01.36 Mot - regen energy
MWh
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full megawatt-
hours. Whenever the counter rolls over, 01.35 Mot - regen
energy GWh is incremented or decremented.
-
-1000…1000 MWh Motoring energy in MWh. 1 = 1 MWh
01.37 Mot - regen energy
kWh
Amount of energy (motoring energy - regenerating energy)
that has passed through the drive in full kilowatt-hours.
Whenever the counter rolls over, 01.36 Mot - regen energy
MWh is incremented or decremented.
-
-1000…1000 kWh Motoring energy in kWh. 10 = 1 kWh
01.61 Abs motor speed
used
Absolute value of 01.01 Motor speed used.-
0.00 … 30000.00 rpm Measured or estimated motor speed. See par.
46.01
01.62 Abs motor speed % Absolute value of 01.03 Motor speed %.-
0.00 … 1000.00% Measured or estimated motor speed. See par.
46.01
01.63 Abs output frequency Absolute value of 01.06 Output frequency.-
0.00 … 500.00 Hz Estimated output frequency. See par.
46.02
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen