Parameters 237
30.13 Minimum frequency Defines the minimum allowed frequency.
WARNING! This value must not be higher than
30.14 Maximum frequency.
WARNING! This limit is effective in frequency
control mode only.
-50.00 Hz;
-60.00 Hz
(95.20 b0)
-500.00…500.00 Hz Minimum frequency. See par.
46.02
30.14 Maximum frequency Defines the maximum allowed frequency.
WARNING! This value must not be lower than
30.13 Minimum frequency.
WARNING! This limit is effective in frequency
control mode only.
50.00 Hz;
60.00 Hz
(95.20 b0)
-500.00…500.00 Hz Maximum frequency. See par.
46.02
30.15 Maximum start
current enable
A temporary motor current limit specifically for starting can
be defined by this parameter and 30.16 Maximum start
current.
When this parameter is set to Enable, the drive observes
the start current limit defined by 30.16 Maximum start
current. The limit is in force for 2 seconds after initial
magnetization (of an asynchronous induction motor) or
autophasing (of a permanent magnet motor), but not more
often than once in every 7 seconds. Otherwise, the limit
defined by 30.17 Maximum current is in force.
Note: The availability of a start current higher than the
general limit depends on drive hardware.
Disable
Disable Start current limit disabled. 0
Enable Start current limit enabled. 1
30.16 Maximum start
current
Defines the maximum start current when enabled by
parameter 30.15 Maximum start current enable.
-
0.00...30000.00 A Maximum motor start current. 1 = 1 A
30.17 Maximum current Defines the maximum allowed motor current. 0.00 A
0.00…30000.00 A Maximum motor current. 1 = 1 A
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals