Publication 1734-UM014A-EN-P - November 2010
90 Adapter Web Dialogs
3. From the Diagnostic Messaging page, click Submit to see values similar
to that shown.
Work with the
Configuration Pages
To work with the Configuration pages, follow these procedures.
IMPORTANT
The values on these pages are in non-volatile memory. Changes to
these parameters do not take effect until you reset or cycle power
through the I/O adapters.
IMPORTANT
If you set the value of the I/O adapters switch to 888 and then
power cycle the module, the following occurs:
The DHCP Enabled function is enabled (set to True).
The Ethernet link is negotiated automatically. The Auto
Negotiate function is set to True.
The web server is enabled. The Disabled Web Server function
is disabled.
The Ethernet port are disabled. Both ports are re-enabled
once the switches are returned to their previous value and
power is cycled.
The password for this page resets to the factory default whih
is "password".
Note the value of the switches before you enter the 888 value
because you must return the adapter to those values once this
process is complete.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley POINT I/O and is the answer not in the manual?

Allen-Bradley POINT I/O Specifications

General IconGeneral
BrandAllen-Bradley
ModelPOINT I/O
CategoryI/O Systems
LanguageEnglish

Related product manuals