Publication 1747-RM001G-EN-P - November 2008
SLC Passthru Communications 14-7
DH-485 with S:34/0=0 or for DF1 Full-duplex with S:34/5=1, then a ‘+’ sign
will appear to the left of the SLC 5/03 icon. Clicking on the ‘+’ sign will
expose a DH-485 or DF1 network underneath the SLC 5/03 icon. Clicking on
the ‘+’ sign to the left of the DH-485 or DF1 network will result in RSWho
browsing for nodes 0 to 31 on the DH-485 network or for node 1 on the DF1
network.
Refer to the steps on page 14-13 for browsing multiple nodes when channel 0
is configured for DF1 Half-duplex Master or DF1 Radio Modem.
SLC 5/03 Passthru Error Codes
A SLC 5/03 passthru processor may respond to a MSG instruction or RSLinx
with error codes of 20H or 30H, under the following conditions.
• A packet is received in either channel to be passed through to the other
channel’s DH-485 network, but the DH-485 node at the remote station
address is not currently present in the other channel’s DH-485 active
node table (30H).
• A remote packet is received in either channel where the remote link ID
doesn’t equal either channel’s link ID (20H).
• A remote packet is received in either channel to be passed through to
the other channel’s DH-485 network, with a remote station address that
is equal to the other channel’s DH-485 address (20H).
• A remote packet is received in either channel to be passed through to
the other channel’s DH-485 network, with a remote station address that
is greater than 31 (20H).
• A DF1 packet is received in channel 0 to a valid DH-485 destination
address with S:34/6=1 and the Local Passthru Queue is full (20H).